M‐ThermalSplit

56 201909
MideaM‐ThermalSplitServiceManual
4.11 H6,HHTroubleshooting
Digitaldisplayoutput

Description
H6indicatesaDCfanerror.
HHindicatesthatH6protectionhasoccurred10timesin2hours.WhenHHerroroccurs,amanualsystemrestartis
requiredbeforethesystemcanresumeoperation.ThecauseofHHerrorshouldbeaddressedpromptlyinorderto
avoidsystemdamage.
M‐ThermalSplitstopsrunning.
ErrorcodeisdisplayedonoutdoorunitmainPCBanduserinterface.
Possiblecauses
DCfanwireisloosed.
Highwindspeed.
Fanmotorblockedorhasfailed.
Invertmoduledamaged.
MainPCBisdamaged.
