M‐ThermalSplit
20190959
4.13 H8Troubleshooting
Digitaldisplayoutput
Description
Pressuresensorerror.
M‐ThermalSplitstopsrunning.
ErrorcodeisdisplayedonoutdoorunitmainPCBanduserinterface.
Possiblecauses
Pressuresensornotconnectedproperlyorhasmalfunctioned.
OutdoorunitmainPCBisdamaged.
Procedure
H8
No

Highpressuresensorconnectionon
outdoorunitmainPCBisloose
Yes
Ensurethesensorisconnectedproperly
No

Highpressuresensorhasshort‐circuited
orfailed
1
Yes
Replacethesensor
No

ReplaceoutdoorunitmainPCB
Notes:
1. Measuretheresistanceamongthethreeterminalsofthepressuresensor.IftheresistanceisoftheorderofmegaOhmsorinfinite,thepressuresensor
hasfailed.ThepressuresensorconnectiononeachtypeofoutdoorunitmainPCBislabeledinFigure4‐2.2inPart4,2.3"MainPCBsforRefrigerantSystem,
InverterModule".
