4.14 P0,HPTroubleshooting
Digitaldisplayoutput
Description
P0 indicates suction pipe low pressure protection. When the suctionpressurefallsbelow0.14MPa,thesystem
displaysP0protectionandM‐ThermalSplitstopsrunning.Whenthepressurerisesabove0.3MPa,P0isremovedand
normaloperationresumes.
HPindicatesP0protectionhasoccurred3timesin60minutes.WhenanHPerroroccurs,amanualsystemrestartis
requiredbeforethesystemcanresumeoperation.
ErrorcodeisdisplayedonoutdoorunitmainPCBanduserinterface.
Possiblecauses
Lowpressureswitchnotconnectedproperlyorhasmalfunctioned.
Insufficientrefrigerant.
Lowpressuresideblockage.
PoorevaporatorheatexchangeinheatingmodeorDHWmode.
Insufficientwaterflowincoolingmode.
OutdoorunitmainPCBdamaged.