M‐ThermalSplit
62 201909
MideaM‐ThermalSplitServiceManual
4.15 P1Troubleshooting
Digitaldisplayoutput
Description
Dischargepipehighpressureprotection.Whenthedischargepressurerisesabove4.2MPa,thesystemdisplaysP1
protectionandM‐ThermalSplitstopsrunning.Whenthedischargepressurefallsbelow3.2MPa,P1isremovedand
normaloperationresumes.
ErrorcodeisdisplayedonoutdoorunitmainPCBanduserinterface.
Possiblecauses
Pressuresensor/switchnotconnectedproperlyorhasmalfunctioned.
Excessrefrigerant.
Systemcontainsairornitrogen.
Highpressuresideblockage.
Poorcondenserheatexchange.
OutdoorunitmainPCBdamaged.