M‐ThermalSplit
20190963
Procedure
P1
Highpressureswitchconnectionor
pressuresensorconnectiononoutdoor
unitmainPCBisloose
1
Yes
Ensurethepressureswitchisconnected
properly
No
Pressuresensorhasshort‐circuitedor
failed
2
Yes
Replacethepressuresensor
No
Thehighpressuresideisblocked,caused
bycrushedorbentpipeorblockedEXV
3
Yes
Inspectthesystemandfixtheerror
No
Theheatexchangeispoor
4
Yes
Inspectthesystemandfixtheerror
No
Thewaterflowrateisnotsufficientin
coolingmode
5
Yes
Inspectthewatersystemandfixthe
error
No
ReplaceoutdoormainPCB
Notes:
1. HighpressureswitchconnectionisportCN13onthemaincontrolboardofoutdoorunit(labeled10inFigure4‐2.2inPart4,2.3"MainPCBsforRefrigerant
System,InverterModule".PressuresensorconnectinisportCN4onthemaincontrolboardofoutdoorunit(labeled15inFigure4‐2.2inPart4,2.3"Main
PCBsforRefrigerantSystem,InverterModule"
2. Measuretheresistanceamongthethreeterminalsofthepressuresensor.IftheresistanceisoftheorderofmegaOhmsorinfinite,thepressuresensor
hasfailed.
3. Highpressuresideblockagecausesdischargetemperaturetobehigherthannormal,dischargepressuretobehigherthannormalandsuctionpressureto
belowerthannormal.
4. Inheatingmodecheckwatersideheatexchanger,waterpiping,circulatorpumpsandwaterflowswitchfordirt/blockages.Incoolingmodecheckairside
heatexchanger,fan(s)andairoutletsfordirt/blockages.
5. Check waterpressureon themanometer.Ifthewaterpressureisnot>1bar,waterflowisinsufficient.RefertoFigure2‐1.6and2‐1.7inPart2,1.2
“HydronicBoxLayout”.