M‐ThermalSplit
20190965
Procedure
P3
No

Thecondenserheatexchangeispoor
1
Yes
Inspectthesystemandfixtheerror
No

Thehighpressuresideisblocked,caused
bycrushedorbentpipeorblockedEXV
2
Yes
Inspectthesystemandfixtheerror
No

Invertermodulehasshort‐circuited
3
Yes
Replacetheinvertermodule
No

Compressorhasmalfunctioned
4
Yes
Replacethecompressor
No

ReplaceoutdoormainPCB
Notes:
1. Inheatingmodecheckwatersideheatexchanger,waterpiping,circulatorpumpsandwaterflowswitchfordirt/blockages.Incoolingmodecheckairside
heatexchanger,fanandairoutletsfordirt/blockages.
2. Highpressuresideblockagecausesdischargetemperaturetobehigherthannormal,dischargepressuretobehigherthannormalandsuctionpressureto
belowerthannormal.
3. Setamulti‐metertobuzzermodeandtestanytwoterminalsofPNandUVWoftheinvertermodule.Ifthebuzzersounds,theinvertermodulehas
short‐circuited.
4. Thenormalresistancesoftheinvertercompressorare0.7‐1.5ΩamongUVWandinfinitebetweeneachofUVWandground.Ifanyoftheresistances
differfromthesespecifications,thecompressorhasmalfunctioned.