MideaM‐ThermalSplitServiceManual
4.17 P4Troubleshooting
Digitaldisplayoutput
Description
Dischargetemperatureprotection.
When the compressor the discharge temperature rises above 115°C, the system displays P4 protection and
M‐Thermal Split stops running. When the discharge temperature fallsbelow90°C,P4isremovedandnormal
operationresumes.
ErrorcodeisdisplayedonrefrigerantsystemmainPCBanduserinterface.
Possiblecauses
Temperaturesensorerror
Highpressuresideblockage.
Poorcondenserheatexchange.
OutdoorunitmainPCBdamaged.