M‐ThermalSplit
20190967
Procedure
P4


Dischargepipetemperaturesensor
connectiononoutdoorunitmainPCBis
loose
1
Yes
Ensurethetemperaturesensoris
connectedproperly
No

Backupelectricheaterwateroutlet
temperaturesensorconnection,
domestichotwatertanktemperature
sensorconnectionorwatersideheat
exchangerwateroutlettemperature
sensorconnectiononhydronicboxmain
PCBisloose
2
Yes
Ensurethetemperaturesensoris
connectedproperly
No

Temperaturesensorhasshort‐circuited
orfailed
3
Yes
Replacethesensor
No

Highpressureswitchconnectionor
pressuresensorconnectiononoutdoor
unitmainPCBisloose
4
Yes
Ensurethepressureswitchisconnected
properly
No

Pressuresensorhasshort‐circuitedor
failed
5
Yes
Replacethepressuresensor
No

Thehighpressuresideisblocked,caused
bycrushedorbentpipeorblockedEXV
4
Yes
Inspectthesystemandfixtheerror
No

Thecondenserheatexchangeispoorin
heatingmode
5
Yes
Inspectthesystemandfixtheerror
No

Thewaterflowrateisnotsufficientin
coolingmode
6
Yes
Inspectthewatersystemandfixthe
error
No

ReplaceoutdoormainPCB
Notes:
1. Discharge pipe temperature sensor connection is port CN8 on the outdoor unit main PCBs (labeled 11in Figure 4‐2.2in Part4, 2.3 "Main PCBs for
Midea CAC Confidential