MideaM‐ThermalSplitServiceManual
Situation 2: L1 or L2 error appears after the compressor has been running for a period of time and the compressor
speedisover20rps
L1/L2
RelayonoutdoorunitmainPCBisopen
Yes
ReplacetheoutdoorunitmainPCB
No
Replacetheinvertermodule
2
Notes:
1. IfthefanmotorisrunningandtheDCvoltagebetweenterminalsPandNoninvertermoduledeclined,Relayonthemaincontrolboardofoutdoor
unitisopen.
2. Whenreplacinganinvertermodule,alayerofthermallyconductivesilicagelshouldbepaintedonIPMmodule(onthereversesideoftheinvertermodule
PCB).RefertoFigure4‐4.1.
relay