M‐ThermalSplit
20190975
L1/L2troubleshooting
ThenormalDCvoltagebetweenterminalsPandNoninvertermoduleis310Vinstandbyand380Vwhenthefanmotoris
running.Ifthevoltageislowerorhigherthanthenormalvoltage,theunitdisplaysanL1orL2error.
Figure4‐4.2:Invertermoduleterminals

UVWN
P
Situation1:L1orL2errorappearsimmediatelyaftertheoutdoorunitispowered‐on
L1/L2


Powersupplyisabnormal
Yes
Re‐starttheunitoncethepowersupply
hasreturnedtonormal
No

Replacetheinvertermodule
1

Notes:
1. Whenreplacinganinvertermodule,alayerofthermallyconductivesilicagelshouldbepaintedontheIPMmodule,IGBT,diode,brigderectifer(onthe
reversesideoftheinvertermodulePCB).RefertoFigure4‐4.1.

N