EasyManua.ls Logo

Midea M-Thermal Series - Page 75

Midea M-Thermal Series
86 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
M‐ThermalSplit
74 201909
MideaM‐ThermalSplitServiceManual
Situation3:L0orL4errorappearsafterthecompressorhasbeenrunningforaperiodoftimeandthecompressor
speedisover60rps
L0/L4


Invertermodulehasoverheated
Yes
Repaintthethermallyconductiesilica
gelontheIPMmodule,IGBT,diode,
brigderectifer
(onthereversesideof
theinvertermodulePCB)
1
No

Invertermoduleisover‐current
2
Yes
Replacethecompressor
No

Replacetheinvertermodule
3

Notes:
1. RefertoFigure4‐4.1.
2. Use clip‐on ammeter to measure the compressorcurrent, if thecurrent is normal indicatesthe invertermodule isfailed, ifthe currentis abnormal
indicatesthecompressorisfailed.
3. Whenreplacinganinvertermodule,alayerofthermallyconductivesilicagelshouldbepaintedonthePFCandIPMmodules(onthereversesideofthe
invertermodulePCB).RefertoFigure4‐4.1.
Situation4:L0errorappearsoccasionally/irregularly
L0


Theoutdoorunitventilationisnotgood
Yes
Ensureenoughspaceforunitventilation
Midea CAC Confidential

Related product manuals