MideaM‐ThermalSplitServiceManual
Situation3:L0orL4errorappearsafterthecompressorhasbeenrunningforaperiodoftimeandthecompressor
speedisover60rps
L0/L4
Invertermodulehasoverheated
Yes
Repaintthethermallyconductiesilica
gelontheIPMmodule,IGBT,diode,
brigderectifer
(onthereversesideof
theinvertermodulePCB)
1
No
Invertermoduleisover‐current
2
Yes
Replacethecompressor
No
Replacetheinvertermodule
3
Notes:
1. RefertoFigure4‐4.1.
2. Use clip‐on ammeter to measure the compressorcurrent, if thecurrent is normal indicatesthe invertermodule isfailed, ifthe currentis abnormal
indicatesthecompressorisfailed.
3. Whenreplacinganinvertermodule,alayerofthermallyconductivesilicagelshouldbepaintedonthePFCandIPMmodules(onthereversesideofthe
invertermodulePCB).RefertoFigure4‐4.1.
Situation4:L0errorappearsoccasionally/irregularly
L0
Theoutdoorunitventilationisnotgood
Yes
Ensureenoughspaceforunitventilation