M‐ThermalSplit
20190973
Figure4‐4.1:Replacinganinvertermodule
Paint a layer of thermally conductive
silicagelonthePFCmodule
Paint a layer of thermally conductive
silicagelontheIPMmodule
Situation2:L0orL4errorappearsimmediatelyafterthecompressorstartsup
L0/L4


UVWwirebetweeninvertermoduleand
compressorisnotconnectedproperly
1
Yes
EnsureUVWwireisconnectedproperly
No

Invertermoduleisdamaged
2
Yes
Replacetheinvertermodule
3
No

Compressorhasmalfunctioned
4
Yes
Replacethecompressor
No

ReplacetheoutdoorunitmainPCB
Notes:
1. ConnecttheUVWwirefromtheinvertermoduletothecorrectcompressorterminals,asindicatedbythelabelsonthecompressor.
2. MeasuretheresistancebetweeneachofU,VandWandeachofPandNontheinvertermodule.Alltheresistancesshouldbeinfinite.Ifanyofthemare
notinfinite,theinvertermoduleisdamagedandshouldbereplaced.Referto
Figure4‐2.2or4‐2.4inPart4,2.1“OutdoorUnitPCBs”.
3. Whenreplacinganinvertermodule,alayerofthermallyconductivesilicagelshouldbepaintedontheIPMmodule,IGBT,diode,brigderectifer(onthe
reversesideoftheinvertermodulePCB).RefertoFigure4‐4.1.
4. Thenormalresistancesoftheinvertercompressorare0.7‐1.5ΩamongUVWandinfinitebetweeneachofUVWandground.Ifanyoftheresistances
differfromthesespecifications,thecompressorhasmalfunctioned.
Midea CAC Confidential