M‐ThermalSplit
20190979
Procedure
Pd


Airsideheatexchangerrefrigerantoutlet
temperaturesensorisloose
1
Yes
Ensurethetemperaturesensoris
connectedproperly
No

Airsideheatexchangerrefrigerantoutlet
temperaturesensorhasshort‐circuited
orfailed
2
Yes
Replacethetemperaturesensor
No

Theairsideheatexchangerheat
exchangeispoor
3
Yes
Inspectthesystemandfixtheerror
No

Thefanorfanmotorisblockedor
damaged
Yes
Inspectthesystemandfixtheerror
No

ReplaceoutdoormainPCB
Notes:
1. AirsideheatexchangerrefrigerantoutlettemperaturesensorandoutdoorambienttemperaturesensorconnectionportareCN9ontheoutdoorunitmain
PCB(labeled12inFigure4‐2.2inPart4,2.3"MainPCBsforRefrigerantSystem,InverterModule")..
2. Measuresensor resistance.If the resistanceis toolow, the sensorhasshortcircuited.Iftheresistanceisnotconsistentwith thesensor’s resistance
characteristicstable,thesensorhasfailed.RefertoPart2,1.1“OutdoorUnitLayout”andtoTable4‐5.1inPart4,5.1“TemperatureSensorResistance
Characteristics”.
3. Checkairsideheatexchanger,fanandairoutletsfordirt/blockages.
