M‐ThermalSplit

80 201909
MideaM‐ThermalSplitServiceManual
4.22 PPTroubleshooting
Digitaldisplayoutput
Description
Watersideheatexchangerinlettemperatureishigherthanoutlettemperatureinheatingmode.
M‐ThermalSplitstopsrunning.
ErrorcodeisdisplayedonhydronicboxmainPCBanduserinterface.
HbindicatesPPhasdisplayed3times.
Possiblecauses
Temperaturesensornotconnectedproperlyorhasmalfunctioned.
4‐wayvalveisblockedordamaged.
HydronicboxmainPCBdamaged.
