M‐ThermalSplit
20190981
Procedure
PP


Watersideheatexchangerwaterinlet/
outlettemperaturesensorisloose
1
Yes
Ensurethetemperaturesensoris
connectedproperly
No

Watersideheatexchangerwaterinlet/
outlettemperaturesensorhas
short‐circuitedorfailed
2
Yes
Replacethetemperaturesensor
No

The4‐wayvalveisblockedordamaged
3
Yes
Replacethe4‐wayvalve
No

ReplaceoutdoormainPCB
Notes:
1. watersideheatexchangerwaterinlettemperaturesensorandwatersideheatexchangerwateroutlettemperaturesensorconnectionsareportCN6on
thehydronicboxmainPCB(labeled11inFigure4‐2.1inPart4,2.2"MainPCBforHydronicSystem").
2. Measuresensor resistance.If the resistanceis toolow, the sensorhasshortcircuited.Iftheresistanceisnotconsistentwith thesensor’s resistance
characteristicstable,thesensorhasfailed.RefertoPart2,1.2“Hydronic BoxLayout” and to Table 4‐5.1to4‐5.2 in Part 4, 5.1“TemperatureSensor
ResistanceCharacteristics”.
3. Restarttheunitincoolingmodetochangetherefrigerantflowdirection.Iftheunitdoesnotoperatenormally,the4‐wayvalveisblockedordamaged.