DM16-01.01.11-01en   Service manual 
Multi DC inverter R410A. Outdoor unit    31 
Bit4 
Frequency limit caused by T2. 
Bit5=1, Bit3=1, 
Bit1=1. 
It means 
frequency limit 
caused by T4,T3 
and current. 
Bit3 
Frequency limit caused by T3. 
Bit2 
Frequency limit caused by T5. 
Bit1 
Frequency limit caused by current 
Bit0 
Frequency limit caused by voltage   
43  Average value of T2  (Sum T2 value of all indoor units)/( number of indoor units in good 
connection)(cooling:T2B, heating:T2) 
44  Outdoor unit fan motor state  Fan off:0, High speed:1, Med speed:2, Low speed:3 Breeze:4, Super 
breeze:5 
45  The last error or protection code  00 means no malfunction and protection 
 
 
10.5 Protection 
10.5.1 Three minutes delay at restart for compressor. 
10.5.2 Temperature protection of compressor discharge. 
When the compressor discharge temp. is getting higher, the running frequency will be limited as below rules: 
T5
Compressor off
Frequency lim it
Normal
Frequency holding
 
10.5.3 Low voltage protection 
VOLTAGE
No limit
VOLT_LTM_FREQ1_ADD
VOLT_LTM_FREQ2_ADD
 
Note: if the low voltage protection occurs and not resumes within 3min, it will keep the protection always 
after restart the machine.   
10.5.4 Compressor current limit protection 
Temperature interval.of current limit is same as range of T4 limited frequency.