2. Refrigerant charging 
 
Procedure: 
1). Connect the charge hose to the charging cylinder; open the 2-way valve and the 3-way valve 
Connect the charge hose which you disconnected from the vacuum pump to the valve at the bottom of 
the cylinder. If the refrigerant is R410A, make the cylinder bottom up to ensure liquid charge. 
2). Purge the air from the charge hose 
Open the valve at the bottom of the cylinder and press the check valve on the charge set to purge the air 
(be careful of the liquid refrigerant). 
3) Put the charging cylinder onto the electronic scale and record the weight. 
4). Open the valves (Low side) on the charge set and charge the system with liquid refrigerant 
If the system cannot be charge with the specified amount of refrigerant, or can be charged with a little at 
a time (approximately 150g each time) , operating the air conditioner in the cooling cycle; however, one 
time is not sufficient, wait approximately 1 minute and then repeat the procedure. 
5).When the electronic scale displays the proper weight, disconnect the charge hose from the 3-way 
valve’s service port immediately 
If the system has been charged with liquid refrigerant while operating the air conditioner, turn off the air 
conditioner before disconnecting the hose. 
6). Mounted the valve stem caps and the service port 
Use torque wrench to tighten the service port cap to a torque of 18N.m. 
Be sure to check for gas leakage