Part 2 - Engineering Data
Table 2-5.3: MC-SU90-RN1L heating capacity
Ambient
temp.
(°C)
Chilled water outlet temperature (°C)
30.00 35.00 40.00 45.00 50.00 55.00
TC PI TC PI TC PI TC PI TC PI TC PI
kW kW kW kW kW kW kW kW kW kW kW kW
-20.00 55.21 23.46 46.32 23.36 37.63 22.86 - - - - - -
-15.00 62.23 23.93 51.23 23.29 42.32 24.89 35.87 25.17 - - - -
-7.00 70.86 22.24 62.32 23.97 54.12 27.06 43.84 26.16 36.23 24.15 - -
2.00 86.74 26.27 82.46 29.45 78.56 34.16 71.90 33.50 54.26 30.15 35.41 23.66
7.00 98.22 29.36 95.11 30.19 92.65 30.88 90.07 33.63 85.32 31.6 68.16 26.64
15.00 90.32 25.81 86.23 26.1 83.36 26.46 78.66 29.13 74.53 27.61 48.36 21.98
20.00 85.63 23.79 82.45 24.25 78.56 23.81 74.36 27.54 72.32 26.78 21.15 11.47
25.00 82.42 22.04 78.63 22.46 74.56 23.30 72.21 22.56 69.97 25.34 27.86 11.74
30.00 78.22 20.52 74.23 20.62 68.44 20.61 64.12 22.89 56.23 20.07 24.26 11.84
Abbreviations:
TC: Total capacity (kW)
PI: Power input (kW)
Notes:
1. Performance specifications measured with water pump operating at rated water flow rate.