Light Commercial R410A on-off DM17-01.01.08en
185
c. Overload of current
Yes
Yes
Replace the main PCB
No
Check if the operation condition is
normal, especially the outdoor unit?
Check if the compressor is running
Yes
Yes
Turn on the units and check if the
problem remains
Yes
Check if the voltage of the power
su
pp
l
y
is too low
No
Replace the outdoor fan
Yes
Check if the capillary is blocked
No
No
There is some air mixed inside the
refrigerant system
Evacuate the system and
re
charge refrigerant
Regulate the power supply
Correct the operation condition
Replace the capillary
Check if the outdoor fan is defective
Replace the compressor
No