R410A All DC Inverter Mini VRF                                                                                                                            MCAC-VTSM-2014-10 
90                                                                                                                                                                                            Troubleshooting 
7.10 P2: Low pressure protection (for all models)   
When the pressure is lower than 0.05MPa, the system will display P2 protection, the ODU in standby. When 
the pressure is higher than 0.15MPa, P2 disappears and resumes normal operation. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
   
Whether wiring connection between low pressure switch and 
PCB is connected well or properly. 
Whether the low pressure switch is damaged. 
Confirm: short-circuit low pressure switch and check 
whether the system can work normally. 
Check whether the cooling system can work as normal. 
Check whether the outdoor ambient temperature is too low. 
Whether refrigerant system leaks. 
Leakage  detecting:  add  nitrogen  or  refrigerant 
into  the  system.  “si”,”si”  will sound  evidently  if 
leaks heavily.  Use soap water(the combination 
of water and detergent ) or electronic detector   
to detect if leaks slightly. 
 
Whether the refrigerant pipe is blocked. 
Remove  the  refrigerant  pipe  and  then  use  high 
pressure  nitrogen  or  refrigerant  to  blow  the  pipe. 
Vacuum the pipe then add the refrigerant again. 
Replace low pressure. 
switch. 
Whether EXV works properly or stuck or blocked 
Replace the throttle parts. 
Whether the reversion of the four-way valve is well 
or mixed up with air or blocked.