MCAC-2008-11 Air-cooled Modular Chiller
64
Operation procedure of units information querying
1. Press [QUERY] entering Check status.
2. Press [ADDRESS+] or [ADDRESS-] button, select the unit you are wanted to query.
3. Press [PAGEUP/TEMP+)] or [PAGEDOWN/TEMP-] button to query the units information, which includes
outdoor ambient temperature T4, pipe temperature T3, setting temperature Ts, CEB out water temp. TB,
online quantity and compressor current, etc.
Operation procedure of system information querying
1. Press [PAGEUP/TEMP+] or [PAGEDOWN/TEMP-] button in the main page, system information could be
queried.
Operation procedure of water temperature setting
1. Press [TEMP SET] button of wire controller when background light is on.
2. Press [PAGEUP/TEMP+] or [PAGEDOWN/TEMP-] button select your require water temperature. Once
selected upon, temperature value will blinks a couple of seconds then confirm it.
3. KJR-08B/BE temperature range:
Cooling: 5~17
Heating: 45~50
Fault alarm handing
When unit fails or the wire controller detects failure of communication with the outdoor units, the indicator
blinks. After all faults of the system and the wire controller are eliminated, the indicator stops blinking. The
fault indicator and the operation indicator share the same LCD.