Do you have a question about the Midea MOBA02-09HFN1-QRD0GW and is the answer not in the manual?
Brand | Midea |
---|---|
Model | MOBA02-09HFN1-QRD0GW |
Category | Air Conditioner |
Language | English |
Failure to observe a warning may result in death. Install according to national regulations.
Failure to observe a caution may result in injury or equipment damage. Follow manual instructions.
Read safety precautions. Improper installation may cause electrical shock, fire, or damage.
Securely install unit to prevent falling. Avoid interference with TVs/radios. Ground if on metal.
Avoid wires, plumbing, and other sensitive components when drilling the wall hole.
Be careful not to dent or damage piping while bending, as it affects unit performance.
Choose a location with adequate space, ventilation, and protection from wind and debris.
Field piping by licensed technician. Prevent refrigerant concentration hazards. Avoid contamination.
Measure, cut, and prepare refrigerant pipes. Ensure proper flaring and connection.
Properly flare pipe ends with flare nuts and insulating material for efficient operation.
Ensure no refrigerant leaks after installation. Ventilate area immediately if a leak occurs.
Connect copper pipes, apply oil, align, and tighten flare nuts to specified torque.
Disconnect power. Use qualified technician. Ensure separate circuit and secure connections.
Strictly follow the wiring diagram. Keep interconnection cable away from hot copper tubes.
Ensure the system is safe and leak-tight by pressure testing above maximum allowable pressure.
Ventilate area, evacuate non-essential personnel, and wear safety goggles during pressure testing.
Increase pressure gradually, check for leaks, and hold pressure for 15 minutes for strength test.
Use appropriate vacuum pump. Do not vacuum outdoor unit. Check for leaks and avoid using refrigerant to evacuate.
Connect manifold gauge and vacuum pump, open low pressure valve, and evacuate to -76cmHG.
Charge after vacuum/leak test. Do not exceed max quantity. Use appropriate refrigerant. Use protective gear.
Confirm units installed correctly, piping/wiring connected, no obstacles, no leaks, and correct voltage.
Failure to perform test run may result in unit damage, property damage, or personal injury.
Open valves, turn on power, set to COOL mode, and check indoor/outdoor unit operations.
Do not use ignition sources near refrigerant. Keep sources away. Survey area for hazards. Display NO SMOKING signs.
Follow procedures for removal, purging with inert gas, and evacuation. Do not use compressed air or oxygen.
Follow requirements for contamination, cylinder handling, earthing, and leak testing.
Remove refrigerants safely using appropriate cylinders and equipment. Do not mix refrigerants.