MCAC-UTSM-2008-05 Capacity Tables
Ceiling and Floor Type 23
7.3 MUB-12HRDN1:
Cooling:
Indoor temperature(°CWB)
14.00 16.00 18.00 19.00 20.00 22.00 24.00
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
Outdoor
temperature
(°C DB)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
21.00 2.42 0.42 2.86 0.53 3.30 0.63 3.50 0.68 3.70 0.74 3.78 0.74 3.86 0.75
23.00 2.42 0.45 2.86 0.56 3.30 0.67 3.50 0.73 3.70 0.79 3.78 0.79 3.86 0.80
25.00 2.42 0.48 2.86 0.60 3.30 0.72 3.50 0.78 3.70 0.84 3.78 0.85 3.86 0.85
27.00 2.42 0.52 2.86 0.64 3.30 0.77 3.50 0.84 3.70 0.90 3.78 0.91 3.86 0.91
29.00 2.42 0.55 2.86 0.69 3.30 0.82 3.50 0.89 3.70 0.96 3.78 0.97 3.86 0.98
31.00 2.42 0.59 2.86 0.73 3.30 0.88 3.50 0.95 3.70 1.03 3.78 1.03 3.86 1.04
33.00 2.42 0.63 2.86 0.78 3.30 0.94 3.50 1.02 3.70 1.09 3.78 1.10 3.86 1.11
35.00 2.42 0.67 2.86 0.83 3.30 1.00 3.50 1.08 3.70 1.16 3.78 1.17 3.86 1.18
37.00 2.42 0.71 2.86 0.88 3.30 1.06 3.50 1.15 3.70 1.24 3.78 1.24 3.86 1.25
39.00 2.42 0.71 2.86 0.89 3.30 1.06 3.50 1.15 3.70 1.24 3.78 1.25 3.86 1.26
41.00 2.42 0.72 2.86 0.89 3.30 1.07 3.50 1.16 3.70 1.25 3.78 1.25 3.86 1.27
43.00 2.42 0.72 2.86 0.90 3.30 1.07 3.50 1.16 3.70 1.26 3.78 1.26 3.86 1.27
Heating:
Indoor temperature(°C DB)
16 18 20 21 22 24
Outdoor air
temp.
TC PI TC PI TC PI TC PI TC PI TC PI
°C DB °C WB kW kW kW kW kW kW kW kW kW kW kW kW
-5 -5.6 3.19 0.99 3.19 1.01 3.19 1.03 3.07 0.98 2.94 0.94 2.69 0.85
-3 -3.7 3.33 1.00 3.33 1.02 3.33 1.04 3.20 1.00 3.06 0.95 2.80 0.86
0 -0.7 3.53 1.02 3.53 1.05 3.53 1.07 3.39 1.02 3.25 0.97 2.97 0.88
3 2.2 3.73 1.05 3.73 1.07 3.73 1.09 3.58 1.04 3.43 0.99 3.14 0.90
5 4.1 3.87 1.06 3.87 1.08 3.87 1.10 3.71 1.06 3.56 1.01 3.25 0.91
7 6 4.00 1.07 4.00 1.10 4.00 1.12 3.84 1.07 3.68 1.02 3.37 0.92
9 7.9 4.00 1.04 4.00 1.06 4.00 1.08 3.84 1.03 3.68 0.99 3.37 0.89
11 9.8 4.00 1.00 4.00 1.02 4.00 1.04 3.84 1.00 3.68 0.95 3.37 0.86
13 11.8 4.00 0.97 4.00 0.99 4.00 1.01 3.84 0.96 3.68 0.92 3.37 0.83
15 13.7 4.00 0.93 4.00 0.95 4.00 0.97 3.84 0.93 3.68 0.88 3.37 0.80