Refrigerant Piping Connection MCAC-UTSM-2008-05
88 Installation
How to connect the pipes
1. Flaring:
Cut a pipe with a pipe cutter.
Insert a flare nut into a pipe and flare the pipe.
Refer to the following table for the dimension of flare nut spaces.
Flare dimension (A)
Pipe gauge Tightening torque
Min Max
Flare shape
Φ6.4
14.217.2 N.m
(144176 kgf.cm)
8.3 8.7
Φ9.5
32.739.9 N.m
(333407 kgf.cm)
12.0 12.4
Φ12.7
49.560.3 N.m
(504616 kgf.cm)
15.4 15.8
Φ15.9
61.875.4 N.m
(630770 kgf.cm)
18.6 19.0
Φ19.1
97.2118.6 N.m
(9901210 kgf.cm)
22.9 23.3
2. Connect the indoor unit at first, then the outdoor unit.
z Bend the tubing in proper way. Do not harm to them.
z The bending angle should not exceed 90.
z Bending position is preferably in the middle of the bendable pipe. The larger the bending radius the
better it is.
z Do not bend the pipe more than three times.
z When connecting the flare nut, coat the flare both inside and outside with either oil or ester oil and
initially tighten by hand 3 or 4 turns before tighting firmly.