61
For 36K-48K Outdoor Unit
No
Problems
Error Code
1
Communication malfunction between indoor and outdoor units.
E1
2
Protection of over-current
F0
3
Open circuit or short circuit of outdoor ambient temperature sensor T4
F1
4
Open circuit or short circuit of condenser coil temperature sensor T3
F2
5
Open circuit or short circuit of Compressor discharge temperature
sensor T5
F3
6
Outdoor unit EEPROM error
F4
7
Outdoor fan speed has been out of control
F5
8
IPM malfunction
P0
9
Over voltage or over low voltage protection
P1
10
High temperature protection of compressor top
P2
11
Outdoor low temperature protection
P3
12
Inverter compressor drive error
P4
13
High temperature protection of indoor coil in heating
J0
14
Outdoor temperature protection of outdoor coil in cooling
J1
15
Discharge temperature protection
J2
16
Protection of active PFC module
J3
17
Communication error between control board and IPM board
J4
18
Hi-pressure switch protection
J5
19
Low-pressure switch protection
J6
20
Outdoor IGBT temperature sensor error
P7
21
AC voltage protection
J8
Outdoor check function
N
Display
Remark
00
Normal display
Display running frequency, running state or malfunction
code
01
Indoor unit capacity demand code
Actual data*HP*10
If capacity demand code is higher than 99, the digital display
tube will show single digit and tens digit. (For example, the
digital display tube show “5.0”,it means the capacity demand
is 15. the digital display tube show “60”,it means the
capacity demand is 6.0)
02
Amendatory capacity demand code
03
The frequency after the capacity requirement
transfer
04
The frequency after the frequency limit
05
The frequency of sending to 341 chip
06
Indoor unit evaporator outlet temperature(heating
T2cooling T2B)
If the temperature is lower than 0 degree, the digital display
tube will show “0”.If the temperature is higher than 70
degree, the digital display tube will show “70”.