62
07
Condenser pipe temperature(T3)
If the temperature is lower than -9 degree, the digital display
tube will show -9”.If the temperature is higher than 70
degree, the digital display tube will show “70”. If the indoor
unit is not connected, the digital display tube will show:
“――”
08
Outdoor ambient temperature(T4)
09
Compressor discharge temperature(T5)
The display value is between 13~129 degree. If the
temperature is lower than 13 degree, the digital display tube
will show “13”.If the temperature is higher than 99 degree,
the digital display tube will show single digit and tens digit.
(For example, the digital display tube show “0.5”,it means
the compressor discharge temperature is 105 degree. the
digital display tube show “1.6”,it means the compressor
discharge temperature is 116 degree)
10
AD value of current
The display value is hex number.
11
AD value of voltage
12
Indoor unit running mode code
Off:0, Fan only 1,Cooling:2, Heating:3
13
Outdoor unit running mode code
Off:0, Fan only 1,Cooling:2, Heating:3, Forced cooling:4
14
EXV open angle
Actual data/4.
If the value is higher than 99, the digital display tube will
show single digit and tens digit.
For example, the digital display tube show “2.0”,it means the
EXV open angle is 120×4=480p.)
15
Frequency limit symbol
Bit7
Frequency limit caused by
IGBT radiator
The display value is
hex number. For
example, the digital
display tube show
2A, then Bit5=1,
Bit3=1, Bit1=1.
It means frequency
limit caused by T4,
T3 and current.
Bit6
Frequency limit caused by
PFC
Bit5
Frequency limit caused by T4.
Bit4
Frequency limit caused by T2.
Bit3
Frequency limit caused by T3.
Bit2
Frequency limit caused by T5.
Bit1
Frequency limit caused by
current
Bit0
Frequency limit caused by
voltage
16
DC fan motor speed
17
IGBT radiator temperature
The display value is between 30~120 degree. If the
temperature is lower than 30 degree, the digital display tube
will show “30”.If the temperature is higher than 99 degree,
the digital display tube will show single digit and tens digit.
(For example, the digital display tube show “0.5”,it means
the IGBT radiator temperature is 105 degree. the digital
display tube show “1.6”,it means the IGBT radiator
temperature is 116 degree)
18
Indoor unit number
The indoor unit can communicate with outdoor unit well.
General:1, Twins:2