MCAC-UTSM-2008-11 Electric Characteristics
Outdoor Units 109
6. Electric Characteristics
Model
Outdoor Unit Compressor OFM
Hz Voltage Min. Max. MSC RLA KW FLA
MOU-12HN1 50 220~240V 198V 254V 29.9 5.3 0.024 0.275
MOUA-18HN1 50 220~240V 198V 254V 36.8 8.7 0.048 0.48
MOUA-24HN1 50 220~240V 198V 254V 61 11.4 0.053 0.67
MOU-30HN1 50 220~240V 198V 254V 97 17.65 0.25 1.38
MOU-30HN1-R 50 380~415V 342V 418V 61 6.58 0.25 1.38
MOU-36HN1 50 220~240V 198V 254V 97 17.65 0.25 1.38
MOU-36HN1-R 50 380~415V 342V 418V 61 6.58 0.25 1.38
MOUA-48HN1-R 50 380~415V 342V 418V 63 8.3 0.065+0.065 0.7+0.7
MOUA-60HN1-R 50 380~415V 342V 418V 67 9.77 0.065+0.065 0.7+0.7
Remark:
MSC: Max. Starting Amps. (A)
RLA: Rated Locked Amps. (A)
OFM: Outdoor Fan Motor.
FLA: Full Load Amps. (A)
KW: Rated Motor Output (kW)
7. Operation Limits
Operation mode Outdoor temperature()℃ Room temperature()℃
Cooling operation 18~43 17~30
Heating operation -7~24 17~30
10 15 25 30 3520
15
20
25
30
35
40
45
Indoor temperature(℃ WB)
Outdoor temperature(
℃
DB)
STD
Cooling
10 15 25 30 3520
-10
-5
0
5
10
15
20
Indoor temperature(℃ DB)
Outdoor temperature(℃ WB)
STD
Heating
25