MCAC-UTSM-2008-11 Capacity Tables
Indoor Units 15
7.2 Heating Capacity
MCA-12HRN1
Heating Outdoor conditions
Indoor Conditions (DB) (kW) 24/18ºC DB/WB 7/6ºC DB/WB 2/1ºC DB/WB -5/-6ºC DB/WB
15ºC
TC
5.20 4.20 3.44 3.12
Input
1.13 0.98 0.84 0.79
20ºC
TC
5.04
4.00
3.24 3.04
Input
1.24
1.05
0.92 0.85
27ºC
TC
4.72 3.76 3.04 2.96
Input
1.31 1.13 1.00 0.92
MCA-18HRN1
Heating Outdoor conditions
Indoor Conditions (DB) (kW) 24/18ºC DB/WB 7/6ºC DB/WB 2/1ºC DB/WB -5/-6ºC DB/WB
15ºC
TC
7.80 6.30 5.16 4.68
Input
2.05 1.77 1.52 1.43
20ºC
TC
7.56
6.00
4.86 4.56
Input
2.24
1.90
1.67 1.54
27ºC
TC
7.08 5.64 4.56 4.44
Input
2.38 2.05 1.81 1.67
Remark:
TC: Total capacity ; kW
SC: Sensible heat capacity ; kW
Input: Input power ; kW