MCAC-UTSM-2008-11 Capacity Tables
Indoor Units 69
MUB-24HRN1
Cooling
Cooling Outdoor conditions (DB)
Indoor Conditions (kW) 21ºC 28ºC 35ºC 43ºC
21/15ºC DB/WB
TC 7.31 6.96 6.60 6.32
SC 5.41 5.36 5.28 5.31
Input 2.24 2.43 2.54 2.62
24/17ºC DB/WB
TC 7.53 7.17 6.82 6.39
SC 5.64 5.59 5.52 5.37
Input 2.38 2.54 2.65 2.78
27/19ºC DB/WB
TC 7.67 7.31 7.10 6.60
SC 5.67 5.63 5.54 5.41
Input 2.43 2.57 2.70 2.84
32/23ºC DB/WB
TC 7.81 7.53 7.38 6.82
SC 6.64 6.55 6.50 6.34
Input 2.54 2.65 2.84 2.94
Heating
Heating Outdoor conditions
Indoor Conditions (DB) (kW) 24/18ºC DB/WB
7/6ºC DB/WB 2/1ºC DB/WB -5/-6ºC DB/WB
15ºC
TC 9.88 7.98 6.54 5.93
Input 3.02 2.60 2.24 2.10
20ºC
TC 9.58 7.60 6.16 5.78
Input 3.30 2.80 2.46 2.27
27ºC
TC 8.97 7.14 5.78 5.62
Input 3.50 3.02 2.66 2.46
Remark:
TC : Total capacity ; kW
SC: Sensible heat capacity ; kW
Input: Input power ; kW