R410A 380~415V 3Ph 50Hz TempMaker Series Split AC                                           MCAC-UTSM-2014-03 
103 
10.4 Duct type indoor unit malfunction and protection codes 
  Names of indicators in receiving kit 
 
 
Fault or protection meaning 
All lamps 
flashing at 5Hz 
Timer lamp 
flashing at 5Hz 
T1, room temperature sensor, fault of open circuit, short circuit. 
Operation lamp 
flashing at 5Hz 
T2, pipe temperature sensor, fault of open circuit, short circuit. 
Defrosting lamp 
flashing at 5Hz 
Condenser temperature sensor malfunction. 
Alarm lamp 
flashing at 5Hz 
Water-level checking malfunction. (Reserved) 
Operation lamp 
and timer lamp 
flashing at 5Hz 
 
  All lamps flashing at 5Hz