R410A Rooftop Package Unit 60Hz MCAC-RTSM-2014-03
17. Error Code
T2 Evaporator low temp, protection
T3 Condenser high temp, protection
Wired controller input failure
Compressor current protection
Compressor-inhaling low pressure protection
1. Indoor fan failure
Check whether the power supply is normal, each wired port is fastened , the setting and wiring of the wired
controller is right.
Confirm the above and check as the following step.
Yes no
Yes no
Check the PCB, whether there is
208/230 voltage between CN9 and L1.
Cut off the power supply and check
whether the fan capacitor is normal .
Check the PCB, whether there is 24V voltage
between G and C.
Check whether the fuse on the
PCB has fused.
Replace the motor capacitor.
Check whether the
transformer is normal
and the secondary has
24v.
Check the wired
controller and wring.