For 18K units
For 24K units
Model FD FD1
MS9V-24HRDN1-QC2W+MOF-24HDN1-QC2W 90 100
8.4.3.5 High evaporator coil temp.T2 protection:
(1) T2> TEH2, compressor running frequency decreases to the lower level every 20s. If the frequency
decreased to F2 and the T2 still over
TEH2 for 3 minutes, the compressor will stop. If T2 deceased to