lower than 48 , or 48 <T2< TEH2 last for 6 minutes, release the frequency limit control.
(2) If T2>60, stop the compressor and restarts until T2<48.
Note:
TEH2
18K 53
24K 55
8.4.4 Auto-mode
This mode can be chosen with remote controller and the setting temperature can be changed between
17~30 .
In auto mode, the machine will choose cooling, heating or fan-only mode according to ΔT (ΔT =T1-Ts).
ΔT=T1-Ts Running mode
ΔT1
Cooling
-1<ΔT 1℃ Fan-only
ΔT≤-1 Heating
Indoor fan will run at auto fan of the relevant mode.
The louver operates same as in relevant mode.
If the machine switches mode between heating and cooling, the compressor will keep stopping for 15
minutes and then rechoose mode according to T1-Ts.
If the setting temperature is modified, the machine will rechoose running function.
8.4.5 Dehumidify mode
8.4.5.1 Indoor fan speed is fixed at breeze and can’t be changed. The louver angle is the same as in
cooling mode.
8.4.5.2 Compressor running rules
8.4.5.3 Room over low temperature protection