Service manual 
36 
 
11.4.3  Auto fan at cooling mode: 
 Condition 
T=Indoor Temp.-Setting Temp. 
Indoor fan speed 
T<1.5℃ Low 
1.5℃<T<4℃ Mid. 
Room temp. up 
 
T>4℃ High 
T> 3℃ High 
1℃<T<3℃ Mid. 
Room temp. down 
T<1℃ Low 
11.4.4  Anti-freezing control to indoor evaporator at cooling mode( T: evaporator temp. ) 
 Evaporator Temp. Compressor 
0℃<T< 4℃  Decrease frequency of compressor  
T< 0℃ Off 
11.4.5 Current protection 
 Model Current  Compressor 
I>18 A  Off 
14.5A<I<18A  Decrease frequency of 
compressor 
Current up  MSH-18HRIN1
I< 12.0A  On 
I>17.5 A  Off 
14.0A<I<17.5A  Decrease frequency of 
compressor 
Current down  MSH-18HRIN1
I< 11.5A  On 
11.4.6  Rated capacity test 
Set mode to cooling mode 
Set temp. to 17°C 
Set fan speed to high speed 
Push turbo button 5 times in 10 seconds. 
Using special remoter controller   
After 5 hours, cancel rated capacity test 
Turbo function 
Increasing frequency of compressor 
After operating 30 minutes, return automatically to the mode and temp. previously selected. 
11.5. Dehumidifying  mode 
11.5.1  The 4-way valve is off   
11.5.2  the indoor fan is fixed in breeze speed 
11.5.3  Compressor run in low frequency 
11.5.4  Low room temperature protection: 
11.5.5 When room temperature decreases to below 10℃, compressor and outdoor fan will stop 
(indoor fan is Breeze). Dehumidifying operation will be resumed when room temperature restores to 
over 12℃. 
11.5.6  At dehumidifying mode, the anti-freezing function of the indoor heat exchanger is the same as 
that of cooling mode. 
11.6. Heating  mode 
11.6.1. Generally, the 4-way valve is open at heating mode, but it is closed at defrosting. 4-way valve 
must delay 2 minutes compared with compressor if the compressor changed into non-heating mode 
or turned off. 4-way valve doesn't delay in dehumidifying mode. 
11.6.2. Generally, the outdoor fan is turned off with the on-off action of compressor in heating mode, 
except for the defrosting mode or the end of defrost. 
11.6.3. Action of compressor and outdoor fan motor at heating mode: compressor must run for 7 
minutes after starting and then judge temperature. Meanwhile other protections are still valid.