Service manual 
46 
 
 
 
          No 
 
 
 
   
 
 
   
 
                    
 
 
 
     
 
 
 
 
 
 
 
 
 
 
 
13.1.10  
Display LED STATUS 
P3  Outdoor low temp. protection 
 
This is optional, factory standard unit has not this function.   
Unit stops when outdoor temp. is low than -15°C and lasting time more than 60 minutes, and unit 
runs again when outdoor temp. more than    -12°C. 
 
 
   
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Does compressor operate? 
Is refrigerant circulation volume normal? 
Gas charging 
Is abnormality the same after gas charging 
Check refrigerant system (such as clogging of 
Is protector normal? 
Check the outdoor main PCB 
Replace protector 
No 
Yes  
Yes 
No  
No  
Is the outdoor temp. low than -15°C? 
Is the outdoor temp sensor right according to the table in clause 12 
Replace the outdoor main board 
No 
Yes 
Is the connection good? 
Yes 
Connect and test again. 
No 
Replace the outdoor main PCB.