Midea R22 T1 side-discharge duct manual MCAC-RTSM-201301-01
22
Insert a flare nut into the pipe and flare the pipe.
Put the connecting tubing at the proper position, wrench the nuts with hands, then fasten it with a
wrench. Too large torque will harm the bellmouthing and too small will cause leakage, so it is
needed to determine the torque according to the table.
After the pipes between the indoor unit and outdoor unit are connected, replenish compressed
niltrogen to perform airtight test.
The test is performed by using the compressed niltrogen 2.94MPa(30kg/cm
2
g)
Tighten the spool of the gas valve and liquid valve before compressing the nitrogen.
Compress the nitrogen at the air vent of the gas valve.
The gas valve and liquid valve are closed in the process of compressing the nitrogen.
Notes:
Do not use oxygen, flammable gas or toxic gas in the airtight test.
3.5 Vacuum
From the following table, select a method of expelling air.
Length of connective pipe (Single pass)
Procedure of expelling air
Use refrigerant in the outdoor unit.
Use vacuum pump or refrigerant tank.
Notes:
If the air conditioner is relocated, be sure to use a vacuum pump or refrigerant tank to expel air.