Electrical Control Function   
236  Electrical Control 
1.3.7.3  The  operating  time  for  sleep  mode  is  7 
hours,  after  which,  the  unit  exits  this  mode  and 
switches off. 
1.3.7.4 The timer setting is available in this mode. 
 
1.3.8 Auto-Restart function 
The  indoor  unit  has  an  auto-restart  module  that 
allows the unit to restart automatically. The module 
automatically  stores  the  current  settings  (not 
including  the  Swing  setting)  and,  in  the  case  of  a 
sudden  power  failure,  will  restore  those  setting 
automatically within 3 minutes after power returns. 
 
1.3.9  Drain  Pump  Control  (For  Duct  and 
Cassette) 
Use the water-level switch to control drain pump. 
The  system  checks  the  water  level  every  5 
seconds. 
----When  the  A/C  operates  in  cooling  (including 
auto  cooling)  or  forced  cooling  mode,  the  pump 
begins  running  immediately  and  continuously  until 
cooling stops. 
----If  the  water  level  increases  up  to  the  control 
point, the LED displays an alarm code and the drain 
pump  opens  and  continually  monitors  the  water 
level. If the water level falls and LED alarm code is 
no  longer  displayed  (drain  pump  close  delay  is  1 
minute),  the  unit  goes  back  into  its  last  mode. 
Otherwise,  the  entire  system  (including  the  pump) 
stops and the LED displays an alarm again after 3 
minutes.