b. Incorrect connection: 
 
Advantages of correct connection: 
1. No back flow. 
2. The slope of two pipes can be regulated separately. 
Disadvantages of incorrect connection:   
1. Drainage interference.   
2. If the fluid volume of one side is greater it will flow to areas with less volume, thus creating back flow into 
areas of the system with less drainage. 
3. Suspender spacing:   
In  general,  horizontal  spacing  is  0.8m-1m  and  vertical  spacing  is  1.5m-2.0m.  Each  vertical  pipe  shall  be 
equipped with not less than two suspenders. Over spacing of suspenders on horizontal piping leads to sagging, 
and creates to air resistance. 
4. The highest point of drainage piping shall be designed with air hole to ensure that condensation can be 
discharged smoothly. The outlet air hole shall face down to prevent dirt entering piping. 
5. After finishing connection, conduct water passing test and overflowing water test to check the smoothness of 
drainage and ensure there is no leakage. 
6.  Use  appropriate  adhesive  for  thermal  insulation  materials  seam,  and  then  bind  with  rubber  or  plastic 
adhesive tape. The width of the adhesive tape shall not be less than 50mm to ensure firm hold and prevent 
condensation. 
7.  The  air  conditioner  drainage  pipe  shall  be  installed  separately  with  other  waste,  rainwater  and  other 
drainage piping. 
8. The slope of drainage pipe shall be kept above 1/100. 
 
9. In case 1/100 slope cannot be met, consider using a larger-sized pipe and its diameter to create slope.