R410A All DC Inverter V5 X Series 50Hz      MCAC-VTSM-2015-10 
142 Troubleshooting 
4.7  E8: Faulty outdoor unit address 
The error will only display on faulty slave unit, all the ODUs will be on standby. 
 
 
 
4.8  xE9: Driver model is mismatched (when X is 1, it refers to A system; 2 refers to B system) 
 
 
   
E8: Faulty outdoor unit address 
The ODU's address is more than 3 or 
be set repeatedly 
The addresses should be set less 
than 3 and differently 
Outdoor main PCB is damaged 
Replace the outdoor main PCB 
The communication wires H1, H2 and 
E are short circuited or disconnected. 
(measure the resistance between H1, 
H2andE, if it is zero or very low, this is 
indication of short circuiting; use a 
multi-meter to test the communication 
wires, if it doesn’t have belling sound, 
this is indication of disconnecting) 
Replace or reconnect the 
communication wires 
E9: Driver model is mismatched 
Power on the outdoor unit immediately 
after it is powered off 
If the outdoor unit is powered off, the 
unit should be powered on after the 
digital tube is powered off 
Outdoor main PCB is damaged 
Replace the outdoor main PCB