MCAC-VTSM-2015-10      R410A All DC Inverter V5 X Series 50Hz 
Troubleshooting 137 
3.  Troubleshooting 
4.1  E0: Communication error between outdoor units 
The error will only display on faulty slave unit, all the ODUs will be on standby. 
 
 
 
 
   
E0: Communication error between outdoor units 
ODU addresses (ENC1) are set incorrectly (the 
master unit address should be set as 0, slave units 
addresses should be set from 1 to 3, and the 
addresses should not be repeated in one system) 
ODU communication wires are connected incorrectly 
(all the wires for H1, H2, E connections should be 
3-core shielded wire, the wiring should be polarity 
connection (H1 connect to H1, H2 connect to H2), 
the wiring should not be short circuited) 
Outdoor main PCB is damaged 
Replace the communication 
wires with 3-core shielded 
wire, reconnect the