V6-i VRF 50/60Hz 
    87 
Part 
6 - Diagnosis and Troubleshooting
 
 Procedure 2.9.5
 
 
Note: 
1.  The DC bus wire should run from the N_in terminal on the inverter module, through the current sensor (in the direction indicated by the 
arrow on the current sensor), and end at the N_out terminal on the inverter module. 
Figure 6-2.2: DC detection wire connection method 
 
 
 
   
F1 error
Compressor inverter module wiring is 
loosened
Reconnect cables based on 
wiring diagram
Reactor and DC bus wiring is incorrectly
1
Reconnect the reactor and 
DC bus wire based on wiring 
diagram
The power supply is abnormal
No
No
Yes
Yes
Disconnect the 
power supply
Check the power supply 
equipment
Yes
Replace the inverter module
No