6 - Diagnosis and Troubleshooting
 
 L1: DC bus low voltage protection 2.13.7
 
 
 
Note: 
1.  The  normal  DC  voltage  between  terminals  P  and  N  on  inverter  module  should  be  450-650V.  When  the  voltage  is  lower  than  350V,  L1 
protection will be appeared.   
Figure 6-2.6: Inverter module terminals 
 
   
L1 protection
The power supply is abnormal
Check the power supply 
equipment
No output from bridge rectifier
Replace the inverter module
No
No
No
Yes
Yes
Yes
Yes
The DC bus voltage (P, N) is abnormal
1
The reactor performs well
Replace the 
reactor
No