EasyManuals Logo

Midea MV8M-140WV2N1 User Manual

Midea MV8M-140WV2N1
130 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #106 background imageLoading...
Page #106 background image
V8 Mini R410A VRF 50Hz
104
Midea
V8 Mini
Series Engineering Data Book
5.6 Watertightness Test and Water Flow Test
Once installation of a drainage piping system is complete, watertightness and water flow tests should be performed.
Watertightness test
Fill the piping with water and test for leakages over a 24-hour period.
Water flow test (natural drainage test)
Slowly fill the drainage pan of each indoor unit with at least 600ml of water through the inspection port and check
that the water is discharged through the outlet of the drain piping.
Caution
The drain plug in the drainage pan is for removing accumulated water prior to performing indoor unit
maintenance. During normal operation, the drain should be plugged to prevent leakage.
Notes for installers

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Midea MV8M-140WV2N1 and is the answer not in the manual?

Midea MV8M-140WV2N1 Specifications

General IconGeneral
BrandMidea
ModelMV8M-140WV2N1
CategoryAir Conditioner
LanguageEnglish

Related product manuals