V8 Mini R410A VRF 50Hz 
    111 
Part 3 - System Design and Installation 
Table 3-8.1: Communication connection between ODU and IDUs 
Communication connection 
type 
All V8 indoor units and unified power 
supply 
All V8 indoor units and separate power 
supply 
400 
(1 repeaters are required) 
All 3
rd
 generation indoor unit or 
3
rd
  generation  indoor  unit  +  V8  indoor 
units 
Once there is 2
nd
 generation indoor unit 
in the system 
 
Figure 3-8.3: Example of indoor unit and outdoor unit communication line connection 
 
 
 
8.3.1 The magnetic ring installation 
For the system, the EMI effect of the communication line PQ (or PQE) can be improved by adding a magnetic ring. The 
magnetic ring needs to be fixed with the communication line (it can be wound for two turns), and placed in the electric 
control box and secured with a wire clamp. 
 
 
 
The communication wires should be connected to the master outdoor unit terminals indicated in Figure 3-8.4 and Table 
3-8.2. 
 
Caution 
 Communication wiring has polarity. Care should be taken to connect the poles correctly.   
 
Figure 3-8.4: Master outdoor unit communication terminals 
Table 3-8.2: Communication connections 
 
Connect to centralized controller 
P Q E 
Communication  connection  between  indoor  units  and 
outdoor unit 
HyperLink  communication  connection  between  indoor 
units and outdoor unit 
Connect to digital energy meter