V8 Mini R410A VRF 50Hz 
    11 
Part 1 
-
 
General Information
 
Capacity index (the capacity in kW multiplied by 10) 
Unit category (W: VRF outdoor unit) 
Type (V2: All DC inverter) 
Power supply 
omit:220-240V, ~, 50Hz 
H:220-240V, 3N~, 50/60Hz 
Refrigerant type (N1: R410A) 
 
 
4 Combination Ratio 
 
 
Table 1-5.1: Indoor and outdoor unit combination ratio limitations 
Minimum 
combination ratio 
Maximum combination ratio 
Standard indoor units only 
Fresh air processing 
units only 
Fresh air processing units and 
standard indoor units together 
Notes:   
1.  All  the indoor  units  connected  should  be  indoor units with  ø5mm  size  copper  tube heater  exchanger.  This  limitation  is  to avoid  too big  indoor unit 
exchanger cause reliability and performance problem. 
2.  If all indoor units in system are V8 Series the total combination ratio must not exceed 160%. If there are non V8 series indoor unit in system the total 
combination ratio must not exceed 130% 
3.  Piping between farthest indoor unit and first indoor branch joint should less than 40m. 
4.  When fresh air processing units are installed together with standard indoor units, the total capacity of the fresh air processing units must not exceed 30% 
of the total capacity of the outdoor units and the total combination ratio must not exceed 100%. 
 
   
Sum of capacity indexes of the indoor units 
Capacity index of the outdoor units