MCAC-HTSM-201506 Midea R410A Direct Heating Commercial Heat Pump 50Hz Technical Manual
20
Communication port for other unit
Communication port for wired controller
System low pressure protection connector
System high pressure protection connector
E-heater Temp. Sensor of refrigerant connector
Water tank (pook) Temp. sensor connector, only the host is valid, the slave is invalid.
Water outlet Temp. sensor connector
E-heater pipe Temp. sensor connector of refrigerant
Water inlet Temp. sensor connector
Discharge Temp. sensor connector
T3: Evaporator Temp. sensor connector
T4: Outdoor ambient Temp. sensor connector
Detection port for compressor current
S3-1: Remote ON/OFF functional status (OFF: inactive (default); ON: active)
S3-2: Defrost periodical choice (OFF: default time by program; ON: 28 minutes)
S3-3,4: Auxiliary heater choice (OFF: indicates 0, ON indicates 1, the factory default
is 00)