Check all the joints with the leak detector or soap water. (See 
Fig.9-6 as a reference illustration) 
 
 
Be sure to with insulating materials cover all the exposed parts 
of the flare pipe joints and refrigerant pipe on the liquid-side and 
the gas-side. Ensure that there is no gap between them. 
 
Incomplete insulation may cause water condensation. 
 
 
 
9.2   Check The Leakage 
9.3   Insulation 
B A 
D 
C 
Check-point of indoor unit 
Check-point of outdoor unit 
 
 A. Lo-stop valve            B. Hi-stop valve 
            C,D. Joints of the connecting pipe to the indoor unit. 
Fig.9-2 
9.   REFRIGERANT PIPE CONNECTION 
9.1  Expel The Air 
Bend the pipe with thumb 
Make the ends 
straight 
Fig.9-1 
Fig.8-3 
Fig.8-2 
Locate The Pipe 
 
Drill a hole in the wall (suitable just for the size of the wall conduit, 
90mm in general), then set on the fittings such as the wall conduit 
and its cover. 
 
Bind the connecting pipe and the cables together tightly with 
binding tapes. Do  not let air  in, which will cause water leakage 
by condensation. 
 
Pass the bound connecting pipe through the wall conduit from 
outside.  Be careful of the pipe all ocation to do no damage to the 
tubing. 
 
Connect the pipes. 
 
Then, open  the stem of stop valves of the outdoor unit to make 
the  refrigerant  pipe connecting the indoor unit with the outdoor 
unit fluently flow. 
 
Be sure of no leakage by checking it with leak detector or soap  
water. 
 
Cover the joint of the connecting pipe to the indoor unit with the 
sound proof/insulating sheath  (fittings),  and bind it well with the 
tapes to prevent leakage. 
 
 
● 
● 
● 
● 
● 
Flaring 
 
Cut a pipe with a pipe cutter. 
 
Insert a flare nut into a pipe and flare the pipe. 
 
90 
lean crude burr 
Then expose the pipe(cover it with tapes after bending). 
 
To prevent collapsing of deforming, please bend the pipe at its 
biggest radius. 
 
Use bender to get a small radius pipes. 
 
Use the market brass pipe. 
Be sure to use the same insulating materials when you buy the 
brass pipe. (More than 9mm thick)  
● 
Use frozen oil 
Fig.8-1 
● 
● 
14 
installation manual 
A 
90+4 
_  
45+2 
_  
Outside diameter 
A(mm) 
Max 
8.7 Φ6.4mm 
Φ9.5mm 
Φ12.7mm 
Φ15.9mm 
Φ19.1mm 
12.4 
15.8 
19.0 
23.3 
8.3 
12.0 
15.4 
18.6 
22.9 
Min 
Table.9-1 
Fig.9-3 
Fig.9-4