SW 2  Difinition 
00 means shutting down the unit
to “stop cold air” at 15℃
00 means the time of stopping 
TERMAL fan is 4 mintue
● 
● 
● 
13.    TROUBLE SHOOTING 
18 
installation manual 
SW5
ON
1 2
SW5
ON
1 2
SW5
ON
1 2
SW5
ON
1 2
SW7
ON
1 2
SW7
ON
1 2
ON
ON
SW5 
Difinition
SW7 
Difinition
0/1
Difinition
SW6
ON
1 2 3
SW6
ON
1 2 3
SW6
ON
1 2 3
00 means temp. compensation 
value is 6℃ under heat mode
1 means old display panel
1 means auto air blow under
   auto  mode
   non-auto  mode
 reserved
 standard 
configuration
 last unit of 
the network
 means 0
 means 1
 
 
For 200T1 unit, two mainboards in the electric control 
should set the code ENC1 to 8; 
 
For 250T1 unit, a mainboard in the electric control should 
set the code ENC1 to 8; the other one should set the code 
ENC1 to 9;       
 
For 280T1 unit, two mainboards in the electric control 
should set the code to 9. 
 
For the same indoor unit, every mainboard must be differ- 
ent indoor unit addresses and network addresses. 
 
When using central controller to control the indoor unit, 
please pay attention to the address setting, as the 220T1, 
250T1 and 280T1 units have two or more mainboards. We 
suggest setting the neighbor address for the mainboards 
in the same indoor unit. When using a central controller for 
controlling, mainboards in the same unit must be opened 
and closed at the same time, for avoiding the unexpected 
incident. 
Table.13-1 
 NO.   Type   Contents 
 LED Lamp flash 
Remarks 
The evaporator  
sensor check  
point is abnoma 
or room temp. 
sensor is  
abnormal. 
Indoor/outdoor unit  
communication  
is abnormal. 
Condenser sensor  
check point is 
abnormal or  
outdoor temp. 
sensor is abnomal 
Water level switch 
 is abnormal  
Mode conflict 
Run lamp 
flashes 
at 2.5Hz. 
The timer lamp 
 flashes at  
 2.5Hz. 
All the indoor 
alarm lamps  
flash at 0.5Hz.  
Alarm lamp 
flashes 
at 2.5Hz. 
Defrost lamp 
flashes at  
2.5Hz. 
After the malfunctions 
disappear, it restores 
automatically. 
 
After the malfunctions  
disappear, it restores 
automatically. 
 
 
After the malfunctions  
disappear, it restores 
automatically. 
 
 
If the malfunctions  
can’t be solved in  
three min. all the  
indoor alarm lamps  
flash at 0.5Hz.Turn  
off the power to restore. 
 
 
When the indoor unit  
turns to heating mode  
or is turned off, the 
alarm will disappear. 
1 
2 
3 
4 
5 
Malfun- 
ction 
Malfun- 
ction 
Malfun- 
ction 
Malfun- 
ction 
Alarm 
7 
6 
Alarm 
EPPROM error 
The indoor unit 
without an add- 
ress when it is  
first time electri- 
fied 
Malfun- 
ction 
 
Defrost lamp 
flashes at  
0.5Hz. 
After the malfunctions  
disappear, it restores 
automatically. 
 
 
Timer lamp  
and run lamp  
flash at 2.5Hz  
together. 
After the malfunctions  
disappear, it restores 
automatically. 
 
 
SW6  Difinition 
CAUTION 
Please adjust the code ENC1 to the suitable position (both 
system A and B should be adjusted for 200T1, 250T1 and 
280T1 indoor unit). 
01 means shutting down the unit
to “stop cold air” at 20℃
10 means shutting down the unit
to “stop cold air” at 24℃
11 means shutting down the unit
to “stop cold air” at 26℃
01 means the time of stopping 
TERMAL fan is 8 mintue
10 means the time of stopping 
TERMAL fan is 12 mintue
11 means the time of stopping 
TERMAL fan is 16 mintue
01 means temp. compensation 
value is 2℃ under heat mode
10 means temp. compensation 
value is 4℃ under heat mode
11 means temp. compensation 
value is 8℃ under heat mode
0 means new display panel
0 means auto air blow under