Attaching wiring   
 
The air conditioner should use separate power supply with rated 
voltage. 
 
The external power supply to the air conditioner should have 
ground wiring, which is linked to the ground wiring of the indoor 
and outdoor unit. 
 
The  wiring  work should be done by qualified persons according 
to circuit drawing. 
 
A leakage protector should be installed according to the National 
Standard concerning electrical appliance. 
 
Be sure to locate the power wiring and the signal wring well to 
avoid cross-disturbance and their contact with connecting pipe 
or stop value body. 
● 
● 
● 
● 
● 
The wiring attached to this air conditioner is 10m long.  Be sure 
to prolong it with wiring of the  same  type  and proper length 
if necessary. Generally, do not twist two wiring together unless 
the joint is soldered well and covered with insulator tape.  
 
Do not turn on the power until you have checked carefully after 
wiring. 
● 
● 
11.   WIRING 
Capacity(KW) 
200/250/280 
16/10 
2.5(<20 m)-4.0(<50 m) 
2.0 
0.75(<1200 m) 
Circuit breaker/fuse  (A) 
Indoor unit power wiring (mm
2
) 
Indoor/outdoor 
connecting 
wiring(mm
2
) 
Ground wiring 
Weak electric signal 
Power 
Phase 
1-Phase 
220-240V~50Hz / 208-230V~60HZ
Frequency and volt 
Table.11-1 
A disconnection device having an air gap contact separation in 
all active conductors should be incorporated in the fixed wiring 
according to the National Wiring Regulation. 
CAUTION 
Fig.11-1 
16 
installation manual 
Communication Wiring Chart   
Communication wiring will be different according to the horse- 
power of air-condictioners. The wiring of 71T1 to 160T1 indoor  
unit, please refer to Fig.11-1, and Fig.11-2 is the communication  
wiring for 200T1, 250T1 and 280T1 indoor unit.   
The reserved function is indicated in broken line table,users can 
select it when necessary. 
CAUTION 
NOTE 
The  air-conditioners can connect with Central Control 
Monitor (CCM). Before operation, please wiring correctly 
and set system address and network address of indoor 
units. 
TO CCM 
COMM.BUS
Please use 3-core shielding wire, and ground the shielding layer.  
TO INDOOR POWER SUPPLY 
220-240V~ 50Hz / 208-230V~60Hz 
L 
N 
 
YELLOW/GREEN 
2 
INDOOR UNIT 
TO INDOOR&OUTDOOR
COMM.BUS
Fig.11-3 
1 
Terminal board diagram 
 
Please refer to the indoor unit wiring diagram for the detailed 
wiring. In accord with the communication wiring, 
terminal board 
wiring is different according to the horsepower of air-condictioners. 
The wiring of 71T1 to 160T1 indoor unit, please refer to Fig.11-3,  
and Fig.11-4 is the wiring for 200T1, 250T1 and 280T1 indoor unit.   
10/10 
INDOOR UNIT
 
XT2  XT3 
(P、Q、E) 
OUTDOOR UNIT
CENTRAL CONTROL 
MONITOR (CCM)
(F
1
、F
2
、E) 
COMPUTER
(X、Y、E) 
INDOOR UNIT
XT2  XT3 
INDOOR UNIT
XT2  XT3 
(X、Y、E) 
(P、Q、E)  (P、Q、E) 
INDOOR UNIT
XT2  XT3 
...... 
Fig.11-2 
71/80/90/112/140/160 
INDOOR UNIT
 
(P、Q、E) 
OUTDOOR UNIT
CENTRAL CONTROL 
MONITOR (CCM)
(F
1
、F
2
、E) 
COMPUTER
(X、Y、E) 
INDOOR UNIT
XT2 
INDOOR UNIT
XT2 
(X、Y、E) 
(P、Q、E) 
INDOOR UNIT
XT2 
...... 
XT2 
The Specification of Power 
Fig.10-2 
Put as deep as possible 
 (about 10mm) 
Downward declivity 
lower than 1/100 
VP30 
Caution: While connecting the drain pipe, please use the drain pipe con-
nect to the secondary water holder simultaneously, for avoiding 
there are little condensate water deposit in the unit when the machine 
is running under the high humidity working condition. 
(X、Y、E) 
220-240V
~
50Hz