Midea
V8
Series VRF Indoor Units
6.1.15 C11 - Duplicate IDU address code
Error code and address
code are displayed
alternately (2)
Error code and address
code flash
simultaneously
Faulty IDU: The fan continues running, and the EXV is closed. Other IDUs of the same system: The fan
continues running, the EXV is closed, and error code "A51" is displayed (V6 platform IDU displays the code
"Ed"). Meaning of the code: ODU fault
ODU of the same system:
stops.
Error code "C26" is displayed (V6 platform ODU displays the code "H7"). Meaning of the code: IDU qty
decrease fault
Repeated address codes for IDU
Duplicate IDU address code
The IDU main control board is damaged.
C11
Locate the
IDU that reports
repeated addresses.
Is the address
repeated?
Reset the address (1)
Replace the main control
board of the IDU (the
communication circuit of the
main control board is
damaged)
Yes
No
Note:
1. The following table shows the number of addresses and address codes for any IDU with different
HP/capabilities.
Address code to be
queried at the
centralized
controller or wired
controller (★)
Address code can
be any integer
from 0 to 63,
denoted by X
The minimum
address code can